HKF Centrifugal fire exhaust fan

HKF Centrifugal fire exhaust fan is a high-safety ventilation solution manufactured by POPULA, a professional 100% direct source manufacturer. Engineered for the critical demands of high-rise civil buildings, this series provides a factory-direct solution for fire safety and emergency smoke extraction in the global B2B market.

Safety & Performance Standards of HKF Centrifugal fire exhaust fan

Sourcing the HKF Centrifugal fire exhaust fan directly from our manufacturing facility ensures that your project complies with the highest fire protection standards. This cabinet-style machine is designed with a specialized single-plate backward tilting impeller, meticulously engineered to minimize pressure loss while maximizing exhaust efficiency during emergency situations.

  • Certified Fire Safety: The HKF Centrifugal fire exhaust fan has passed inspection by the fire product qualification assessment center of the National Emergency Management Department, ensuring fully compliant safety for professional engineering projects.
  • Extreme Temperature Resilience: Engineered for emergency operation, this series can safely function in high-temperature conditions of 280°C for more than 30 minutes, providing critical smoke extraction time.
  • Long-Term Operational Durability: For standard ventilation, the fan is designed for continuous long-term use when gas temperatures are at or below 120°C.
  • High-Rise Smoke Exhaust: Optimized specifically for the fire smoke exhaust and general ventilation requirements of high-rise civil buildings, ensuring the safety of occupants.
  • Low Pressure Loss Design: The multi-wing cabinet structure and backward tilting impeller work together to reduce energy loss and maintain stable airflow during high-demand operation.

With its certified safety performance and robust cabinet construction, the HKF Centrifugal fire exhaust fan is an essential component for modern building safety systems. Trust POPULA for professional technical support and competitive wholesale pricing on all fire-rated centrifugal ventilation solutions.

Parameters
ModelPower(kW)Rotation(r/min)Volume(m³/h)Pressure(Pa)Static Pressure(Pa)
HKF-I-(A)№3.6E-VII0.5512503152~5102300~122290~87
HKF-I-(A)№3.6E-VI0.7514503565~5919405~165390~117
HKF-I-(A)№3.6E-V1.116004035~6531493~201475~142
HKF-I-(A)№3.6E-IV1.518004540~7347624~254600~180
HKF-I-(A)№3.6E-III2.220005043~8163770~314742~222
HKF-I-(A)№3.6E-II322005548~8979932~380898~270
HKF-I-(A)№3.6E-I424006102~98771128~4601086~352
HKF-I-(A)№3.6E5.526006712~108651364~5561314~394
HKF-I-(A)№4.0E-VI0.7512503997~6929467~172452~124
HKF-I-(A)№4.0E-V1.114504636~8038627~231608~166
HKF-I-(A)№4.0E-IV1.516005116~8870764~282740~204
HKF-I-(A)№4.0E-III2.218005756~9979968~357937~257
HKF-I-(A)№4.0E-II320006395~110871194~4401157~317
HKF-I-(A)№4.0E-I422507195~124741512~5571464~401
HKF-I-(A)№4.0E5.524007674~133051720~6341666~456
HKF-I-(A)№4.5E-VI1.112506147~9950467~18846~143
HKF-I-(A)№4.5E-V1.514507140~11558629~255612~192
HKF-I-(A)№4.5E-IV2.216007873~12744765~309744~234
HKF-I-(A)№4.5E-III318008866~14351969~391943~296
HKF-I-(A)№4.5E-II420009847~159391196~4831165~366
HKF-I-(A)№4.5E-I5.5220011076~179291513~6111473~463
HKF-I-(A)№4.5E7.5240011821~191351722~6951676~527
HKF-I-(A)№5.0E-VII2.211209413~14752635~268653~203
HKF-I-(A)№5.0E-VI3125010538~16514791~334777~254
HKF-I-(A)№5.0E-V4145012225~191581065~4501045~341
HKF-I-(A)№5.0E-IV5.5160013484~211311297~5481272~415
HKF-I-(A)№5.0E-III7.5180015170~237751641~6931610~525
HKF-I-(A)№5.0E-II11200016862~264252026~8561988~649
HKF-I-(A)№5.0E-I15225018961~297142563~10832515~821
HKF-I-(A)№5.0E18.5240018522~317062917~12332862~934
HKF-I-(A)№5.6E-VIII2.210009702~15401532~217461~168
HKF-I-(A)№5.6E-VII3112010843~17212668~273579~211
HKF-I-(A)№5.6E-VI4125012139~19268832~340721~263
HKF-I-(A)№5.6E-V5.5145014082~223531120~457970~354
HKF-I-(A)№5.6E-IV7.5160015532~246551361~5561181~431
HKF-I-(A)№5.6E-III11180017476~277401726~7041495~546
HKF-I-(A)№5.6E-II15200019423~308312131~8691845~673
HKF-I-(A)№5.6E-I18.5225021841~346702696~11002335~852
HKF-I-(A)№5.6E22240023306~369943068~12522657~970
HKF-I-(A)№6.0E-VII4100012214~21072686~257671~181
HKF-I-(A)№6.0E-VI5.5112013679~23602861~322842~227
HKF-I-(A)№6.0E-V7.5125015267~263401071~4011049~283
HKF-I-(A)№6.0E-IV11145017710~305551443~5401441~381
HKF-I-(A)№6.0E-III15160019542~337161757~6571718~464
HKF-I-(A)№6.0E-II18.5180021985~379302224~8322174~587
HKF-I-(A)№6.0E-I22200024427~421442745~10272684~725
HKF-I-(A)№6.0E30220026870~463593322~12433248~877
HKF-I-(A)№7.0E-VI5.5100014976~27734789~422771~367
HKF-I-(A)№7.0E-V7.5112016773~31062989~529966~460
HKF-I-(A)№7.0E-IV11125018720~346671233~6601205~574
HKF-I-(A)№7.0E-III15130019469~360541333~7131302~620
HKF-I-(A)№7.0E-II18.5145021715~402141794~9601751~835
HKF-I-(A)№7.0E-I22160023962~443742020~10811973~940
HKF-I-(A)№7.0E30180026957~499202557~13692497~1190
HKF-I-(A)№8.0E-VI5.590017527~33049868~555860~493
HKF-I-(A)№8.0E-V7.5100019474~371211071~6861063~602
HKF-I-(A)№8.0E-IV11112021811~415761334~8601333~756
HKF-I-(A)№8.0E-III15125024341~463991674~10721660~942
HKF-I-(A)№8.0E-II18.5132025704~489971867~11941851~1049
HKF-I-(A)№8.0E-I22145028236~538232252~14412234~1267
HKF-I-(A)№8.0E30160031157~593912743~17552720~1543
HKF-I-(A)№9.0E-VIII7.572022895~40940648~348569~300
HKF-I-(A)№9.0E-VII1183026393~47195860~460756~398
HKF-I-(A)№9.0E-VI1590029692~530941012~540890~468
HKF-I-(A)№9.0E-V18.5100032990~589931249~6671098~577
HKF-I-(A)№9.0E-IV22112036950~660721567~8371377~724
HKF-I-(A)№9.0E-III30125039748~710761952~10431716~902
HKF-I-(A)№9.0E-II37132034246~750562176~11631914~1006
HKF-I-(A)№9.0E-I45145040922~792192625~14032310~1214
HKF-I-(A)№9.0E55160045155~874143038~16242672~1405

Start your hassle-free, no-obligation consultation today.

You don’t need to provide precise airflow or static pressure data. Simply share the ventilation challenges you’re facing—such as workshop size, temperature conditions, or dust levels—and our engineers will handle all the complex calculations and model selection for you. Start a relaxed, no-obligation initial consultation today.